What the sizing estimate assumes
The heating and cooling numbers on an estimate are a sales sizing estimate: a fast room-by-room calculation to help you propose equipment and count registers. It isn't an engineering design. For an unusual home, or when a design is required, check the numbers yourself or have a full load calculation done.
What it works out
For each room, from what you enter about the room, its windows and its doors:
- Heat gain (cooling): through windows (by type and the direction they face), doors, the ceiling, walls and floor, plus people, appliances and air leaking in.
- Heat loss (heating): through walls, the ceiling, the floor, windows and doors, plus air leaking in around windows and doors.
- Airflow and registers: the house's airflow is shared between rooms by their share of the load, and each room's registers are its airflow divided by the airflow per register, rounded up.
The house totals are the sums of the rooms.
What it assumes
- Temperatures: the summer and winter design temperature differences on the estimate, the same for every room.
- Insulation: the R-values you enter for walls, ceiling, floor and doors. A value of 0 counts as no loss or gain through that surface.
- Airflow: 450 CFM per ton of the air handler, and at least 1 ton. Heating airflow is shown as 75% of cooling airflow.
- Vaulted ceilings have 15% more ceiling area.
- Heating: add duct loss (+15%), when it's set for a room, will add 15% to that room's heat loss.
- The room's location (Cooling: ducts in conditioned space; Cooling: ducts in unconditioned space; Attic / top floor; Basement) scales the room's whole cooling estimate. A room with ducts in conditioned space gets the smallest increase, a room with ducts in unconditioned space more, and an attic or top-floor room the most. A basement room has no cooling load at all. The heating estimate isn't affected.
- People and appliances add a set amount of heat each, from the estimate's settings.
- Windows gain heat by type and direction, from fixed tables; sliding windows let in more air than fixed ones.
Starting values
Your company's house defaults fill in a new estimate's settings, such as ceiling height, R-values, design temperatures and airflow per register. They're only starting values: change them on the estimate when the house is different.
Warnings
The estimate warns when an input doesn't make sense, for example when a room's windows and doors are larger than its wall, or when the airflow per register is 0.